💧 Tube Pressure Drop Calculator
Calculate pressure drop inside heat exchanger tubes using Darcy-Weisbach equation.
Inputs
Darcy friction factor. Typical turbulent flow ~0.02
Results
Pressure Drop Profile
Calculator Description
Pressure drop inside a pipe is the energy lost to friction and minor losses as fluid flows through piping or heat-exchanger tubes. It is a key factor setting pump head, pipe diameter and operating cost.
What this calculator finds
Given length L, inside diameter D, velocity v, fluid density ρ and the Darcy friction factor f, it computes the pressure drop ΔP (or head loss h_f) inside the tube — chiefly used for heat-exchanger tube design.
Why it matters
- Sizing required pump/compressor head and power
- Optimizing pipe diameter and velocity (energy vs capital cost)
- Evaluating tube-side pressure loss in heat exchangers
Formula
Darcy-Weisbach Equation
The pressure drop is proportional to the friction factor f, the length-to-diameter ratio L/D, and the dynamic pressure (ρv²/2). Head loss h_f is the same relation divided by g.
- ΔP — Pressure drop [Pa]
- h_f — Head loss [m]
- f — Darcy friction factor (dimensionless)
- L, D — Length and inside diameter [m]
- v, ρ — Velocity [m/s] and density [kg/m³]
- g — Gravitational acceleration (≈ 9.81 m/s²)
How the formula works
- f is set by Reynolds number (Re = ρvD/μ) and roughness; it grows with turbulence.
- Drop scales with v² → doubling velocity quadruples the loss.
- A smaller D raises both L/D and dynamic pressure, sharply increasing loss.
Worked example
For water (ρ = 1000 kg/m³) flowing at 2 m/s in a 50 mm ID, 10 m long tube with f = 0.02: ΔP = 0.02 × (10/0.05) × (1000×2²/2) = 0.02 × 200 × 2000 = 8000 Pa = 8 kPa, with head loss h_f ≈ 0.82 m.
Useful Tips
Practical tips
- Obtain f from the Moody chart or Colebrook–White equation (fully developed turbulent flow).
- Add minor losses (elbows, valves) as equivalent length Le to L.
- Pick diameter within an economic velocity range (water ≈ 1–3 m/s) for balanced cost.
Limitations & cautions
- Valid for single-phase Newtonian fully developed flow; in laminar flow f = 64/Re.
- For non-Newtonian, multiphase or strongly compressible flow, use dedicated correlations.